2.2.3 Mk3 LIMIT connector
LIMIT 1-8 connects limit switches. It’s recommended that a 100nF capacitor is connected
directly across switch terminals.
The 'SHIFT' key toggles limit options using one of two possible configurations. The chosen
configuration determines hardware connections.
Limit switches can be connected in 'Normal' method or 'Single input' method. In software, you can set
this in File/Settings/Limit. If you are using 'Normal' method, 'Single Input' feature must be disabled.
To pause all axes, if certain axes limit switch has been activated, you enable 'Lock Other Axes'.
NORMAL: Each switch is connected to its own pin.
LIMIT 1: Axis 1 negative limit
LIMIT 2: Axis 1 positive limit
LIMIT 3: Axis 2 negative limit
LIMIT 4: Axis 2 positive limit
LIMIT 5: Axis 3 negative limit
LIMIT 6: Axis 3 positive limit
LIMIT 7: Axis 4 negative limit
LIMIT 8: Axis 4 positive limit
SHIFT: Toggle Limit switch options
GND: Ground connections
SHIFT OFF: Axes 1 to 4 limits are selected
SHIFT ON: Axes 5 to 8 limits are selected